Current location:Home> Products&solutions > Transformer on - line monitoring system
ProductsOn-load tap changer (On-load Tap Changer-OLTC) is a key component of on-load tap-changer, and the failure rate is up to 20%, accounting for 40% of the total fault of the on-load tap-changer. The monitoring of the on-load tap-changer is particularly important for reducing the failure rate of the transformer.
The on-load tap-changer on-line monitoring system (IED) obtains data information (current and voltage rms) from the process layer network and obtains the on-load tap-changer gear status from the on-load switch controller and records the number of operations, OLTC anomalies State (such as power failure, refused to move) and other information; the system can increase the controller to achieve on-load tap-changer on-site control and based on network control.
Serial number | Monitoring project | Measuring range |
1 | Number of channels | 2,4,6,8 |
2 | Measuring range | -30℃~200℃ |
3 | Accuracy | 2℃ |
4 | Front panel display | Large1"LED display (per channel) |
5 | Probe signal strength read | All channels have separate signal buttons |
6 | Input power | Universal AC / DC [90-265VAC / DC] power supply |
7 | Number of relays | 6 C-type programmable cooler control and alarm set points |
8 | Temperature data storage | Save the temperature data for more than one year, read once every minute and keep the maximum temperature of each channel until the user is reset |
9 | LED alarm indicator | One for each relay |
10 | System fault relay | 1 type C relay |
11 | System fault indicator | 2 LEDs (green for good operation, red for failure) |
12 | Overvoltage protection | 3000V(IEEE C37.90.1.1989) |
13 | Connector | All ring terminal blocks |
14 | Operating ambient temperature | -40℃~+70℃ |
15 | Storage temperature | -40℃~+85℃ |
16 | communication | Industrial Ethernet / fiber interface, support IEC61850 |